INVESTIGATION ON INDOOR ENVIRONMENT AT OFFICES LOCATED IN HOT HUMID REGION IN JAPAN UNDER THE CONDITION OF POWER SAVING

http://hdl.handle.net/10173/1259
http://hdl.handle.net/10173/1259
548d4347-e68c-4b84-9a13-e9ff1d0fd3ad
名前 / ファイル ライセンス アクション
sms13-8726.pdf sms13-8726.pdf (255.0 kB)
Item type 会議発表論文 / Conference Paper(1)
公開日 2015-02-28
タイトル
タイトル INVESTIGATION ON INDOOR ENVIRONMENT AT OFFICES LOCATED IN HOT HUMID REGION IN JAPAN UNDER THE CONDITION OF POWER SAVING
言語
言語 eng
資源タイプ
資源タイプ識別子 http://purl.org/coar/resource_type/c_5794
資源タイプ conference paper
著者 HASHIDA, Tomokazu

× HASHIDA, Tomokazu

HASHIDA, Tomokazu

Search repository
TAJIMA, Masaki

× TAJIMA, Masaki

TAJIMA, Masaki

Search repository
抄録
内容記述タイプ Abstract
内容記述 According to a research result handled by Ministry of Health, Labour and Welfare, measurement values of
temperature, relative humidity and concentration of carbon dioxide (CO2 concentration), which had been
obtained at large buildings, have not met partly the reference values of the Act on Maintenance of Sanitation
in Buildings in Japan recently. At the same time, the government has been requiring power saving activities
for the public after the Great East Japan Earthquake in 2011.
This paper describes the present state of temperature, relative humidity, and CO2 concentration by using
result of continuous measurement at four office rooms located in hot humid region in Japan. Additionally,
result of questionnaire survey about power saving action in each target office room is shown. At one office
room, at which the air conditioning’s setting temperature was as same as the upper limit of the reference of
the Act, mean value of temperature was higher than the reference value in cooling period. In heating period,
the mean value of the measurement result of relative humidity was approximately 30%RH, which is lower
than the lower limit of the reference value of the Act. CO2 concentration was influenced by the power saving
action. The measurement value of the concentration was proportionate to the strength of the power saving
activities. Moreover, the measurement values are compared with Japan wide data obtained before the
earthquake. The result of the comparison derives that the measured indoor environment are poorer quality.
The quality seems that it was caused by the energy saving actions by analysing questionnaire survey results.
書誌情報 Society for Social Management Systems Internet Journal

巻 9, 発行日 2014-12
著者版フラグ
出版タイプ VoR
出版タイプResource http://purl.org/coar/version/c_970fb48d4fbd8a85
出版者
出版者 Society for Social Management Systems
戻る
0
views
See details
Views

Versions

Ver.1 2023-05-15 13:11:23.401768
Show All versions

Share

Mendeley Twitter Facebook Print Addthis

Cite as

エクスポート

OAI-PMH
  • OAI-PMH JPCOAR 2.0
  • OAI-PMH JPCOAR 1.0
  • OAI-PMH DublinCore
  • OAI-PMH DDI
Other Formats
  • JSON
  • BIBTEX

Confirm


Powered by WEKO3


Powered by WEKO3